Changing Rosslare Keypad Transmission Format
When connecting a Rosslare Key/Pin Pad / Reader to Qumulex you will need to modify the Transmission format. It defaults to a proprietary method that is not readable by Qumulex directly.
To make it compatible with Qumulex, perform the following steps after the Keypad is wired and powered.
To make it compatible with Qumulex, perform the following steps after the Keypad is wired and powered.
- Press the "#" key 4 times to enter programming mode (Left LED will turn off and Right LED will turn red)
- Enter the 4-digit programming code (default is 1234). If valid code is entered, the right light turns green.
- Press the "1" key to program the PIN transmission format
- Press the 9 Key to set the Transmission to Weigand 4bit
- The keypad will automatically go back to Idle mode
To enter your PIN key in a valid PIN and then hit the "#" button to complete the request.